Send Message
I'm Online Chat Now

PVC Cu Cable 0.6 1kV

PVC Cu Cable 0.6 1kV
PVC Cu Cable 0.6 1kV

Large Image :  PVC Cu Cable 0.6 1kV

Product Details:

Place of Origin: Wuhan, China
Brand Name: Green Song
Certification: IEC, ASTM,BS,NF,VDE,NZS,ANSI ,DIN JES,JEC(CSA).
Model Number: Low voltage

Payment & Shipping Terms:

Price: Negotiable
Packaging Details: optional flame retardant type
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Detailed Product Description
High Light:

PVC Cu Cable 0.6 1kV

,

Low Voltage PVC Cu Cable

,

XLPE Insulated Cable 0.6 1kV

 

  • Application

This product is suitable for power lines with rated voltage of 0.6 / 1kV and below, for power transmission, suitable for laying in hotels, stations, airports, high-rise buildings, chemical industry, petroleum platform, power station, subway, tunnel and other fixed laying places.

  • Cable Performance

The long-term allowable operating temperature of the cable shall not exceed 70℃, and the short-time working temperature shall not over 130℃.

The ambient temperature of the installation should not be lower than 0℃.

Minimum bending radius during cable installation: single-core cable not exceeding 15D (D is cable diameter), multi-core cable not exceeding 12D (D is cable diameter)

3. Cable Construction

3.1 Conductor adopts a compact fan or compact round structure, VV 32 is copper conductor and VLV 32 is aluminum conductor.

3.2 70℃ PVC insulation material is used for insulation, and the insulation thickness is shown in Table 1.

 

Table 1

Nominal section mm2 Nominal insulation thickness mm Nominal section mm2 Nominal insulation thickness mm
1.5 2.5 0.8 150 1.8
4 6 1.0 185 2.0
10 16 1.0 240 2.2
25 35 1.2 300 2.4
50 70 1.4 400 2.6
95 120 1.6    

3.3 Cable armored material: galvanized steel wire is used, and the single core cable used for AC system adopts non-magnetic armored material.

3.4 The sheath is made of 70℃ PVC sheath material.

3.5 Nominal diameter and weight

 

 

Table 2

specifications

Core * section

Nominal

outer diameter mm

Nominal Weight kg/km Specification Core*section Outer Diameter mm Nominal weight kg/km
VV32 VLV32 VV32 VLV32
1*1.5 10.8 223 209 2*1.5 13.8 361 343
1*2.5 11.2 245 225 2*2.5 14.6 408 378
1*4 12.1 290 260 2*4 17.2 623 575
1*6 12.6 325 283 2*6 18.3 707 635
1*10 13.6 395 328 2*10 20.3 879 757
1*16 14.6 481 378 2*16 22.8 1173 980
1*25 16.2 622 462 2*25 26.0 1528 1220
1*35 17.9 865 646 2*35 27.7 1792 1368
1*50 19.6 1055 760 2*50 33.0 2541 1967
1*70 21.3 1312 891 2*70 37.0 3303 2475
1*95 24.0 1788 1204 2*95 41.3 4132 2980
1*120 25.4 2075 1343 2*120 45.3 5190 3739
1*150 28.0 2464 1557 2*150 50.1 6196 4395
1*185 30.1 2916 1785 2*185 54.3 7308 5058
1*240 32.9 3605 2109 2*240 60.3 9049 6066
1*300 36.9 4637 2760 2*300 65.9 10795 7046
1*400 40.5 5641 3250 2*400 74.2 13977 9194
3*1.5 14.3 400 371 4*1.5 15.1 446 408
3*2.5 16.0 567 521 4*2.5 16.9 634 573
3*4 17.9 702 630 4*4 19.0 798 701
3*6 19.0 808 701 4*6 20.3 930 786
3*10 21.3 1026 844 4*10 23.5 1329 1085
3*16 24.1 1426 1135 4*16 25.9 1679 1291
3*25 27.6 1890 1429 4*25 29.9 2267 1653
3*35 29.5 2257 1621 4*35 32.0 2739 1891
3*50 34.7 3129 2268 4*50 37.7 3869 2721
3*70 38.5 4050 2808 4*70 42.0 4950 3294
3*95 43.2 5150 3423 4*95 48.7 6826 4523
3*120 47.9 6537 4361 4*120 52.3 8044 5142
3*150 52.5 7767 5065 4*150 58.1 9677 6075
3*185 57.7 9324 5949 4*185 63.7 11660 7160
3*240 64.2 11656 7180 4*240 70.4 14558 8591
3*300 70.2 14015 8392 4*300 79.0 18578 11081
3*400 79.6 18222 11048 4*400 87.2 22740 13174
3*2.5+1*1.5 15.8 501 446 3*2.5+2*1.5 17.4 668 603
3*4+1*2.5 18.5 757 669 3*4+2*2.5 19.3 823 720
3*6+1*4 20.0 897 765 3*6+2*4 21.0 996 840
3*10+1*6 22.8 1257 1038 3*10+2*6 24.0 1386 1132
3*16+1*10 25.3 1591 1240 3*16+2*10 26.7 1778 1366
3*25+1*16 28.9 2117 1560 3*25+2*16 30.6 2380 1725
3*35+1*16 30.4 2468 1735 3*35+2*16 32.0 2723 1893
3*50+1*25 36.1 3469 2454 3*50+2*25 38.7 3999 2830
3*70+1*35 39.9 4474 3020 3*70+2*35 42.5 5030 3364
3*95+1*50 44.8 5724 3709 3*95+2*50 49.5 6934 4633
3*120+1*70 50.1 7371 4781 3*120+2*70 53.8 8387 5382
3*150+1*70 54.6 8599 5483 3*150+2*70 57.3 9514 5985
3*185+1*95 60.2 10469 6519 3*185+2*95 63.5 11712 7186
3*240+1*120 66.2 13078 7878 3*240+2*120 69.6 14586 8660
3*300+1*150 72.5 15601 9077 3*300+2*150 78.2 18420 10995
3*400+1*185 82.0 20191 11891 3*400+2*185 85.8 22375 12950
4*2.5+1*1.5 17.7 688 617 5*1.5 16.8 601 563
4*4+1*2.5 19.7 862 750 5*2.5 17.9 697 630
4*6+1*4 21.3 1028 860 5*4 20.2 889 779
4*10+1*6 24.5 1455 1176 5*6 21.6 1046 878
4*16+1*10 27.3 1863 1415 5*10 25.1 1508 1218
4*25+1*16 31.5 2526 1815 5*16 27.8 1929 1461
4*35+1*16 34.7 3261 2316 5*25 32.4 2649 1900
4*50+1*25 40.1 4318 3016 5*35 36.0 3511 2472
4*70+1*35 44.5 5496 3627 5*50 41.6 4630 3195
3*95+1*50 51.6 7572 4982 5*70 48.0 6421 4351
4*120+1*70 55.8 9048 5732 5*95 53.7 8200 5321
4*150+1*70 60.8 10645 6628 5*120 57.8 9695 6068
4*185+1*95 66.6 12879 7803 5*150 63.9 11688 7186
4*240+1*120 73.4 16222 9530 5*185 69.7 14028 8403
4*300+1*150 82.4 20429 12031 5*240 79.0 18582 11123
3*400+1*185 90.5 24923 14231 5*300 86.5 22414 13041
        5*400 96.1 27629 15672
 

 

 

4. Main performance

4.1 The DC resistance of 20℃ conductor shall meet the requirements of Table 3.

Table 3

nominal cross mm2 1.5 2.5 4 6 10 16 25 35 50
20℃ conductor DC resistance is not over n (Ω / km) copper 12.1 7.41 4.61 3.08 1.83 1.17 0.727 0.527 0.387
aluminium   12.4 7.41 4.61 3.08 1.91 1.20 0.868 0.641
nominal cross mm2 70 95 120 150 185 240 300 400  
20℃ conductor DC resistance is over (Ω / km) copper 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470  
aluminium 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778  

 

4.2 Finished cable shall be subjected to 3.5kV / 5min voltage test without breakdown.

 

Contact Details
Wuhan Green Song Zheng Cable Co.,Ltd

Contact Person: Bill Li

Tel: +8618062506367

Send your inquiry directly to us (0 / 3000)